VALVE TYPE ARRESTER

Saturday, March 21st, 2009

Valve type arresters incorporate non linear resistors and are extensively used on systems, operating at high voltages. Fig 12 (i) shows the various parts of a valve type arrester. It consists of two assemblies (i) series spark gaps and (ii) non-linear resistor discs in series. The non-linear elements are connected in series with the spark gaps. Both the assemblies are accommodated in tight porcelain container. (i) The spark gap is a multiple assembly consisting of a number of identical spark gaps in series. Each gap consists of two electrodes with fixed gap spacing. The voltage distribution across the gap is linearised by means of additional resistance elements called grading resistors across the gap. The spacing of the series gaps is such that it will withstand the normal circuit read more

If you enjoyed this post, make sure you subscribe to my RSS feed! Read more »

EXPULSION TYPE ARRESTER

Saturday, March 21st, 2009

This type of arrester is also called ‘protector tube’ and is commonly used on system operating at voltages up to 33kV. Fig 11(i) shows the essential parts of an expulsion type lightning arrester. It essentially consists of a rod gap AA’ in series with a second gap enclosed within the fiber tube. The gap in the fiber tube is formed by two electrodes. The upper electrode is connected to rod gap and the lower electrode to the earth. One expulsion arrester is placed under each line conductor. Fig11 (ii) shows the installation of expulsion arrester on an overhead line. On the occurrence of an over voltage on the line, the series gap AA’ spanned and an arc is stuck between the electrodes in the tube. The heat of the arc vaporizes some of the fiber of tube walls resulting in the read more

If you enjoyed this post, make sure you subscribe to my RSS feed! Read more »

MULTIGAP ARRESTER

Saturday, March 21st, 2009

Fig 10 shows the multigap arrester. It consists of a series of metallic (generally alloy of zinc) cylinders insulated from one another and separated by small intervals of air gaps. The first cylinder (i.e. A) in the series is connected to the line and the others to the ground through a series resistance. The series resistance limits the power arc. By the inclusion of series resistance, the degree of protection against traveling waves is reduced. In order to overcome this difficulty, some of the gaps (B to C in Fig) are shunted by resistance. Under normal conditions, the point B is at earth potential and the normal supply voltage is unable to break down the series gaps. On the occurrence an over voltage, the breakdown of series gaps A to B occurs. The heavy current after breakdown will read more

If you enjoyed this post, make sure you subscribe to my RSS feed! Read more »

HORN GAP ARRESTER

Saturday, March 21st, 2009

Fig 9 shows the horn gap arrester. It consists of a horn shaped metal rods A and B separated by a small air gap. The horns are so constructed that distance between them gradually increases towards the top as shown. The horns are mounted on porcelain insulators. One end of horn is connected to the line through a resistance and choke coil L while the other end is effectively grounded. The resistance R helps in limiting the follow current to a small value. The choke coil is so designed that it offers small reactance at normal power frequency but a very high reactance at transient frequency. Thus the choke does not allow the transients to enter the apparatus to be protected. The gap between the horns is so adjusted that normal supply voltage is not enough to cause an arc across the read more

If you enjoyed this post, make sure you subscribe to my RSS feed! Read more »

ROD GAP ARRESTER

Saturday, March 21st, 2009

It is a very simple type of diverter and consists of two 1.5 cm rods, which are bent at right angles with a gap in between as shown in Fig 8. One rod is connected to the line circuit and the other rod is connected to earth. The distance between gap and insulator (i.e. distance P) must not be less than one third of the gap length so that the arc may not reach the insulator and damage it. Generally, the gap length is so adjusted that breakdown should occur at 80% of spark-voltage in order to avoid cascading of very steep wave fronts across the insulators. The string of insulators for an overhead line on the bushing of transformer has frequently a rod gap across it. Fig 8 shows the rod gap across the bushing of a transformer. Under normal operating conditions, the gap remains read more

If you enjoyed this post, make sure you subscribe to my RSS feed! Read more »