|
DIFFERENTIAL PROTECTION IN TRANSFORMERSAuthor: arjun
|
|||||||||||||||
|
SL.NO |
POWER TRANSFORMER CONNECTIONS |
CURRENT TRANSFORMER CONNECTIONS |
||
|
PRIMARY |
SECONDARY |
PRIMARY |
SECONDARY |
|
|
1
2
3
4 |
Star with neutral earthed
Delta
Star
Delta
|
Delta
Delta
Star with neutral earthed
Star with neutral earthed
|
Delta
Star
Delta
Star |
Star
Star
Delta
Delta |
1. Another factor, which has to be considered, is the inrush of magnetizing current.
When the transformer is switched to supply the magnetizing current may assume very high values momentarily and may cause operation of the relay even though they are transient. This can be avoided by using relays with time delay characteristics.
Fig 8 shows the differential protection for transformer. In this the power transformer is delta- star connected. On delta side the C.T.s are connected in star and on the star side the C.T.s are connected in delta as in fig. Under normal working conditions the circulating currents caused by the primary and secondary load current in the relay circuit will balance; but under fault conditions the balance will no longer be there and the relay will be energized to trip the circuit breakers on the primary and secondary side
In order to understand the phase difference in the two sides consider fig 8. The primary is connected in delta and the set of current transformers CT1 is connected in star, while the secondary is connected in star and the set of current transformers CT2 is connected in delta. Fig 9 illustrates the vector diagram in reference to primary and secondary sides of current transformer. In fig 9.a IRP, IYP and IBP are the phase currents in the primary side, while IR is the line current on the same side in line R as shown in fig 9.a, the corresponding secondary current of current transformers CT1 on the primary side is in
phase with IR and is represented as IRS in fig 9.b. the current in the secondary side of the power transformer is represented as IR, IY and IB in fig 9.c, the phase current in the secondary winding of the current transformers CT2 is represented as I’R, I’Y and I’B in fig 9.d. the current in pilot wire of CT2 is represented as IRS. Now when we consider fig 9.b and 9.d its clear that the currents in the pilot wires are in phase.
In order to understand the phase difference in the two sides consider fig 8. The primary is connected in delta and the set of current transformers CT1 is connected in star, while the secondary is connected in star and the set of current transformers CT2 is connected in delta. Fig 9 illustrates the vector diagram in reference to primary and secondary sides of current transformer. In fig 9.a IRP, IYP and IBP are the phase currents in the primary side, while IR is the line current on the same side in line R as shown in fig 9.a, the corresponding secondary current of current transformers CT1 on the primary side is in
phase with IR and is represented as IRS in fig 9.b. the current in the secondary side of the power transformer is represented as IR, IY and IB in fig 9.c, the phase current in the secondary winding of the current transformers CT2 is represented as I’R, I’Y and I’B in fig 9.d. the current in pilot wire of CT2 is represented as IRS. Now when we consider fig 9.b and 9.d its clear that the currents in the pilot wires are in phase.
If you enjoyed this post, make sure you subscribe to my RSS feed!
December 13th, 2009 at 11:54 am
thanks for the valuable information given to us
May 14th, 2010 at 7:01 pm
This is very useful information
May 28th, 2010 at 1:41 pm
thanks.
June 7th, 2010 at 8:02 am
Thanks. I like that.